MINERVA MX1000 / MX4000

The MINERVA MX panels are intelligent LPCB EN54 approved panels, which can be networked to provide up to 396 detection loops and installed to BS5839:Pt.1.

  • The MX1000 supports one MX Digital detection loop with up to 250 addressable devices.
  • The MX4000 supports two MX Digital detection loops and can be expanded to four loops supporting up to 1000 addressable devices.

Both panels consist of a strong steel enclosure incorporating a removable chassis plate. The chassis plate holds:

  • PSB800 5A 24V d.c. battery backed power supply and loop booster to EN54:pt.4
  • FIM800 field interface PCB incorporating one or two MX Digital loops
  • CPU800 32 bit processor and memory card
  • Optional network card, additional loop card(s) and remote diagnostic modem
  • Optional IOB800 input/output expansion card mounted on the PSB800

The panel has a strong cast aluminium front door, which incorporates a modular user interface that fully complies with EN54:pt.2. The user interface incorporates the ODM800 operator display module with a 16 x 40-character backlit LCD display, simple alphanumeric keypad, 5 softkeys and a fast access key. The OCM800 operator control module provides all mandatory operator control keys and LED functions including Day/Night switching. Two control keys and 2 indication LEDs are provided for site-specific functions.

Control keys and LEDs are labelled in English according to the default LPCB functionality. The slide in decals can be reversed and alternative text added.

Product Codes

Standard Panels

557.200.001      MX1000 Single Loop Panel – Shallow Back Box
557.200.002     MX1000 Single Loop Panel - Flush Back Box
557.200.003      MX4000 Two to Four Loop Panel – Shallow Back Box
557.200.004    MX4000 Two to Four Loop Panel – Deep Back Box
557.200.009      MX4000 Two to Four Loop Panel - Flush Back Box
557.200.007      MX-BBX-40LED 17Ah battery box with 40 zone LEDs

Options

557.202.006      IOB-800 (8in/8out) expansion board (Max. 24 I/O on main panel)
557.202.007      XLM-MX two loop MX DIGITAL expansion card
557.202.026      TLI-800 ThornNet & MX-NET network card
557.202.036      Remote Diagnostic Modem
557.202.116      Modem lead